Model |
VRU2500 |
Topology |
True On – Line, Double Conversion |
On-Battery Output Waveform |
True Sine Wave |
Number of Phase |
Single (1µ2W + G) |
Input |
|
Maximum Capacity (VA /W) |
2500 VA/1750 W |
Nominal Input Voltage |
230 V |
Input Voltage Regulation |
160 to 276 VAC |
Nominal Input Frequency |
50 / 60 Hz +/- 5Hz |
Input PFC |
>0.98 @ full load |
Input Short Protection |
Circuit Breaker |
Output |
|
Nominal Output Voltage |
208/220/230/240 VAC |
Output Voltage Regulation |
Rated Voltage +/- 2% |
Output THD |
<3%@Linear Load |
High Efficiency Mode (AC to AC) |
>88% |
Crest Factor |
3:01 |
Start on Battery |
Yes |
Output Frequency |
50 / 60 Hz (Autotracking) |
Overload Capability |
Sustaining 50 sec@108% load: 28 sec@110-120% load ; 15 sec @120 – 130% load; 9 sec@140-145% load; Immediate Response@150% load |
Battery |
|
User Replaceable Battery |
96V (2x48 VDC Battery Pack) |
Typical Backup Time (Full/Half Load) |
8/20 minutes |
Battery Type |
Sealed VRLA 12V7AH; Hot Swap |
Recharge Time to 90% |
8 hours |
Extended Battery Cabinet |
Extendible Battery Module in 2U High (Comprises 2 x 48VDC Battery Packs |
Advance Warning Diagnostics |
|
Front Panel Indication |
Front Panel menu driven LCD Monitoring and control panel for all functions |
Audible Alarms |
DC Mode, Low Battery, Voltage / Frequency Error, Charger Fail, High Temp, Over Load, Fault, PFC Overload |
Communication Interface |
|
Communication Port |
RS-232 Port (Standard) : DB9, AS400 , USB Cards (optional) |
SNMP Manageable |
Yes |
Environmental |
|
Operation Temperature |
0-40°c (32-104F) |
Storage Temperature |
-B4415-40°c (5-122F) |
Relative Humidity |
0% to 95% non-condensing |
Audible Noise (at 1 meter from surface of unit) |
|
Mechanical |
|
Dimensions-Rackmount (W x H x D mm) |
426 x 176.8(4U) x 545 mm |
Dimensions -Tower (W x H x D mm) |
176.8 x 426 x 545 mm |
Weight (UPS / Battery Banks) |
13.5 / 32.5 kg |
Total Weight |
46 kg |
Conformance |
|
EMI / RFI Compatibility |
EN50091-2 Class B, EN55022B |
Safety Certifications |
CE,TUV/GS
|